Control I/O Modules via CAN-Bus

CAN module with 10 digital inputs that can be operated as contact or voltage inputs. Suitable for detecting switch states, e.g. for electrical limit switches on ventilation dampers or auxiliary contacts on power contactors. The FDE 4 fieldbus modules are universally applicable input modules which are connected to other modules or a bus master via the CAN-BUS.

Ideal as a complement to our touch panel computers and as an extension to our Tiger DIN-Rail range.

  • Input 10 x analog inputs (temperature and voltage input)
  • (c)CiA standard 2.0B passive
  • Wiring two-wire bus with potential equalization line in bus/line topology
  • Transmission rate 20 - 500 kBit/s (factory setting 125 kBit/s)
  • Dimensions W x H x D 35 x 70 x 65 mm
  • Supply and bus connection terminal 1.5 mm² pluggable (connection terminal and bridge plug as accessories in the packaging)
  • Operating voltage range 20 ... 28 V AC/DC
  • Power consumption 67 mA (AC) / 24 mA (DC)
  • Temperature input for Ni1000 or Pt1000 sensor
  • Operating temperature range -5 °C ... +55 °C
  • Storage temperature range -20 °C ... +70 °C
  • Operation and bus activity: green LED
  • Error messages: red LED

 